Product Profile
3∅ 25 kVA
1∅ 50 kVA CSP
3∅ 50 kVA
3∅ 100 kVA
3∅ 160 kVA
3∅ 250 kVA
3∅ 630 kVA
Any Custom 1∅ or 3∅ up to 20,000kVA
01. Strip-Wound Core
For application of 1-phase or 3-phase compact size transformers with low noise and excellent magnetic circuit characteristics
02. Stacking Core
A mitered core, joined by 45-degree cut silicon steel sheets, with excellent mechanical strength and low iron loss. For the application of high capacity transformers
03. Step-Lap Core
For applications of 1-phase or 3-phase core-type or shell-type transformers of high capacity and voltage. This type of core has high mechanical strength and allows for a smooth magnetic flux path to considerably minimize iron loss
01. Insulation
Pressboard, thermally upgraded insulating Kraft paper, high breakdown resistance transformer oil
02. Bushings
High quality porcelain bushings with optional bushing wells and plug-in bushings upon request. This option allows cables to be inserted directly, with no live parts outside
03. Clamp
Step-lap cores and stacking cores have different clamping arrangements. Sintra’s core clamps are manufactured in-house to be capable of withstanding strong axial electromagnetic force. This is critical in guaranteeing the safety of the transformer in an abnormal event of overload
04. Standard Accessories
Name plate, rating plate, oil level indicator, oil temperature indicator, fill and drain valves, lifting lugs, tap changer, base roller or skid base
05. Accessories for Conventional Tank
Conservator with breather, Buchholz relay, dial-type thermometer with alarm and tripping contacts, bushings cable box, elastimold epoxy resin bushing for HV side
06. Accessories for Hermetically-Sealed Tank
Pressure relief device, pressure vacuum gauge, nitrogen filling valve, dial thermometer with alarm and tripping contacts, bushings cable box, elastimold bushing
Test items include, but are not limited to, the following: